INSTALLATION AND MAINTENANCE INSTRUCTIONS
SK-400-007 1 I56-3433-001R
SPECIFICATIONS
GENERAL
Range: 16 to 230 Feet (5 to 70m); 230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK
Sensitivity: 25% to 50% Total Obscuration in 6 levels
Level 1 = 25%
Level 2 = 30%
Level 3 = 40%
Level 4 = 50%
Level 5 = 30% to 50% (Acclimate)
Level 6 = 40% to 50% (Acclimate)
Spacing: 30 to 60 Feet (9.1 to 18.3m)
Response Time: ALARM - 20 seconds typical
TROUBLE - 30 seconds typical
Trouble Conditions: Beam Blockage (96% or More Obscuration)
Improper Initial Alignment
Self-compensation limit reached (service needed)
In Alignment mode
Test/Reset Features: Integral Sensitivity Test Filter (SK-Beam-T only, requires additional external power supply)
Sensitivity Filter (Incremental scale on reflector)
Local Alarm Test Switch
Local Alarm Reset Switch
Remote Test and Reset Switch Capability (compatible with RTS451/RTS451KEY/RTS151/RTS151KEY)
Indicators: ALARM - Remote Output, Local LED (red)
TROUBLE - Remote Output, Local LED (yellow) Blink Pattern Indicates Trouble Diagnostics
NORMAL OPERATION - Local LED (flashing green with communication)
ALIGNMENT AIDS - Optical Gunsight (coarse adjustment) 00 to 99 Digital Display (fine adjustment)
SENSITIVITY - Digital Display Readout in Percent Obscuration
Style 7 Operation: On-board isolators provide style 7 operation. (may be disabled via shunts on circuit board)
EnvironmEntal
Temperature: –22°F to 131°F (–30°C to 55°C);
NOTE: for applications below 32°F (0°C) see Special Applications section of this manual.
Humidity: 10% to 93% RH Noncondensing
Mechanical
Shipping Weight: 3.9 lbs. (1.77 kg)
Shipping Size: 15˝ × 10.5˝ × 6.5˝ (381mm × 267mm × 165mm)
Mounting: Wall only without optional accessories
Wiring: Plug-in Terminal Blocks (12 to 22AWG)
Adjustment Angle: ±10° Horizontal and Vertical
Paintable Trim Ring: May be painted using enamel or acrylic type paints
Electrical
Voltage: 15 to 32 VDC
Standby Current: Avg. Standby: 2mA Max. (1 communication every 5 sec., LED flashing, SLC @ 24 V)
Max. Alarm (LED on): 8.5mA Max.
Max. Trouble (LED on): 4.5mA Max.
Max. Alignment: 20mA Max.
External Supply (SK-Beam-T only): VO LTAG E - 15 to 32 VDC
CURRENT - 0.5A Max.
Remote Output: (alarm) VOLTAGE - 15 to 32 VDC; NOTE: Output voltage same as device input voltage.
CURRENT - 15mA maximum; 6mA minimum; NOTE: Output current is limited by 2.2Kohm resistor
SK-Beam, SK-Beam-T Single-ended
Reflected Type Projected
Beam Smoke Detector
I56-3433-001R
GENERAL DESCRIPTION
Model SK-Beam/SK-Beam-T is a long range projected beam smoke detector
designed to provide open area protection. It is to be used with UL-listed com-
patible control panels only. The detector consists of a transmitter/receiver unit
and a reflector. Smoke entering the area between the transmitter/receiver and
reflector causes a reduction in signal. When the obscuration reaches alarm
thresholds (chosen at the transmitter/receiver unit), the detector generates
an alarm signal. Complete blockage of the beam causes a trouble signal. Slow
changes in obscuration due to a build up of dirt or dust on the lens of the de-
tector are compensated for by a microcontroller that continuously monitors
the signal strength and periodically updates the alarm and trouble thresh-
olds. When the self-compensation circuit reaches its limit, the detector gen-
erates a trouble signal, indicating the need for service.
Three LEDs on the detector indicate the current status: a red LED for alarm,
a yellow LED for trouble, and a blinking green LED for standby operation.
Note: The panel controls the status of the red and green LEDs. The local
reset button is accessible by removing the outer paintable trim ring. The
yellow LED will blink in specific patterns to provide a diagnostic aid when
12 Clintonville Road, Northford, CT 06472
203.484.7161; Fax: 203.484.7118
www.silentknight.com
Page view 0
1 2 3 4 5 6 ... 14 15

Summary of Contents

Page 1 - Beam Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONSSK-400-007 1 I56-3433-001RSPECIFICATIONSGENERALRange: 16 to 230 Feet (5 to 70m); 230 to 328 Feet (70 to 10

Page 2 - C0306-00

SK-400-007 10 I56-3433-001RAPPENDIX I. OPERATION MODES AND TROUBLESHOOTING GUIDEModes *RedSee Note BelowYellow, Remote Trouble*GreenSee Note BelowRe

Page 3 - C0257-00

APPENDIX II. DETECTOR DRILLING TEMPLATE4.345˝6.190˝ (157 mm) (110 mm)Scale = 1:1SK-400-007 11 I56-3433-001R

Page 4 - REFLECTOR

SK-400-007 12 I56-3433-001R

Page 5 - T3 T2 T1

5.512˝(140mm)8.465˝(215mm)APPENDIX III. REFLECTOR DRILLING TEMPLATEScale = 1:1SK-400-007 13 I56-3433-001R

Page 6

SK-400-007 14 I56-3433-001R

Page 7 - C0266-00

SK-400-007 15 I56-3433-001R ©2009 Honeywell International Inc.Please refer to insert for the Limitations of Fire Alarm SystemsThis projected be

Page 8 - OBSCURATION LEVEL

SK-400-007 2 I56-3433-001Rdiagnosing the cause of a trouble signal. It will also blink the amount of drift compensation that has been used at the co

Page 9

FIGURE 1. SPACING FOR SMOOTH CEILING (SIDE VIEW):1/2 S S12 - 18 IN.(0.3 - 0.46M)WALLC0254-00FIGURE 2. SPACING FOR SMOOTH CEILING (TOP VIEW):16 FT. (5M

Page 10

FIGURE 5A. REFLECTOR MOUNTING GUIDELINESWALLREFLECTORACCEPTABLE MOUNTINGLOCATIONS FOR REFLECTOR1010C0258-00FIGURE 5B. REFLECTOR MOUNTING GUIDELINES10

Page 11 - Scale = 1:1

FIGURE 6. WIRING CONNECTIONS AT DETECTORSLC (–)SLC (+)SLC (–)SLC (+)RESET I NPUTTEST INPUTAUX (–)REMOTE ALARM OUTNOT USEDREMOTE TROUBLE OUTTEST OPTION

Page 12 - SK-400-007 12 I56-3433-001R

STEP 1. COARSE ALIGNMENTRefer to Figures 11 and 12 for this step.1. Insure that both of the optics lock-down screws are loosened so that the optics

Page 13

FIGURE 10. SWITCH LOCATIONS!,)'.-%.43%.3)4)6)494%342%3%4349,%)3/,!4/23(5.433(/7.$)3!",%$#/$%37)4#(4%.3/.%3C0854-00FIGURE 11. ALIGNME

Page 14 - SK-400-007 14 I56-3433-001R

Sensitivity Setting% ObscurationDisplay ReadingAcceptable Distance Between Detector and Reflector (Feet)Acceptable Distance Between Detector and Ref

Page 15 - FCC STATEMENT

SK-400-007 9 I56-3433-001RThese steps include:1. Verify all wiring connections and appropriate power is applied to the detector.2. Ver